Control Tags
- Last UpdatedAug 04, 2025
- 1 minute read
The driver defines a number of tag addresses which can be used to send system information in a control direction. These tags are write-only.
|
Address format |
Plant SCADA type |
IEC 60870 command |
Description |
|---|---|---|---|
|
FORCEGI |
DIGITAL |
Interrogation command |
Writing "1" to this digital register will force a general interrogation of the device. |
|
FORCECS |
DIGITAL |
Clock synchronization command |
Writing "1" to this digital register will force a clock synchronization of the device. |
|
FORCECI |
DIGITAL |
Counter interrogation command |
Writing "1" to this digital register will force a counter interrogation of the device (without freeze or reset of the counters). |
|
COUNTFZ |
DIGITAL |
Counter interrogation command |
Writing "1" to this digital register will perform a counter freeze on the device. |
|
COUNTRS |
DIGITAL |
Counter interrogation command |
Writing "1" to this digital register will perform a counter reset on the device. |
|
COUNTFZRS |
DIGITAL |
Counter interrogation command |
Writing "1" to this digital register will perform a counter freeze and reset on the device. |