The driver defines a number of tag addresses which can be used to send system information in a control direction. These tags are write-only.

Address format

Plant SCADA type

IEC 60870 command

Description

FORCEGI

DIGITAL

Interrogation command

Writing "1" to this digital register will force a general interrogation of the device.

FORCECS

DIGITAL

Clock synchronization command

Writing "1" to this digital register will force a clock synchronization of the device.

FORCECI

DIGITAL

Counter interrogation command

Writing "1" to this digital register will force a counter interrogation of the device (without freeze or reset of the counters).

COUNTFZ

DIGITAL

Counter interrogation command

Writing "1" to this digital register will perform a counter freeze on the device.

COUNTRS

DIGITAL

Counter interrogation command

Writing "1" to this digital register will perform a counter reset on the device.

COUNTFZRS

DIGITAL

Counter interrogation command

Writing "1" to this digital register will perform a counter freeze and reset on the device.