Determine Tag Status

  • Last UpdatedJul 18, 2023
  • 1 minute read

The Tag Status element is used to represent the current status of the tag. The value of this element is affected only for those tag operations that involve a physical device (for example, writing to the Field element will affect the status element, but writing to the Control Mode will not). Tag Status element is reset after I/O server restart. The element value contains a set of bit flags.

The following table describes the Tag Status element:

Reference Syntax

Plant SCADA Data type

Description

TagName.Status

INT

Value of Tag Status element

TagName.Status.V

INT

Value.

A set of bit flags representing the following data:

- 0x1: Read Pending.

- 0x2: Write Pending.

- 0x4: Write Successful.

- 0x8: Write Unsuccessful.

Default value: 0.

TagName. Status.VT

TIMESTAMP

Timestamp of when the value last changed.

TagName.Status.Q

QUALITY

Quality.

TagName.Status.QT

TIMESTAMP

Timestamp of when the quality last changed.

TagName.Status.T

TIMESTAMP

Timestamp of when the element was last updated.