Unit Address
- Last UpdatedDec 13, 2021
- 1 minute read
The I/O Device Address for a Omron CV Series PC is specified as follows:
w/n/u (there are no defaults)
Where
-
w is the FINS network address (1-127)
-
n is the FINS node number (1-126)
-
u is the FINS PC Bus unit number (0-15)
Specify the FINS network address, node number, unit number. The FINS node number must be the same as the IP address node number. The FINS network number must be the same for all ETN's on the Ethernet segment.
Note also there is no relationship between FINS network numbers and IP network numbers.
Some examples:
|
IO Server IP address |
IO Server net mask |
PC node number |
Resultant PC IP address |
|
a.b.c.d |
255.255.255.0 |
10 |
a.b.c.10 |
|
a.b.c.d |
255.255.0.0 |
10 |
a.b.0.10 |