[Alarm]MonitorConnectTimeout
- Last UpdatedJul 19, 2023
- 1 minute read
Defines the amount of time, in seconds, that the server will wait for a monitor connection to occur. If there is no monitor connection between the server you are configuring and the other server in the pair after the defined MonitorConnectTimeout, the other server will regard itself as isolated and will become Primary.
However, if you need the checks to detect lack of communication more quickly, you can reduce the timeout amount. But be aware that if the timeout is too short, a server may regard itself as isolated before it has had time to process a response to a request (or complete the connection establishment process).
Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.
Allowable Values:
0 to 4294967295
Default Value:
30