Timer Objects
- Last UpdatedJul 07, 2025
- 2 minute read
|
Property Mnemonic |
BACnet Data Type |
Plant SCADA Data Type |
Access |
|
ObjectIdentifier |
BACnetObjectIdentifier |
LONG |
ReadOnly |
|
ObjectName |
CharacterString |
STRING |
ReadOnly |
|
ObjectType |
BACnetObjectType |
LONG |
ReadOnly |
|
Description |
CharacterString |
STRING |
Read/Write |
|
PresentValue |
Unsigned |
LONG |
Read/Write |
|
StatusFlags |
BACnetStatusFlags |
STRING |
ReadOnly |
|
EventState |
BACnetEventState |
LONG |
ReadOnly |
|
Reliability |
BACnetReliability |
LONG |
Read/Write |
|
OutOfService |
Boolean |
DIGITAL |
Read/Write |
|
TimerState |
BACnetTimerState |
LONG |
ReadOnly |
|
TimerRunning |
Boolean |
DIGITAL |
Read/Write |
|
UpdateTime |
BACnetDateTime |
STRING |
ReadOnly |
|
LastStateChange |
BACnetTimerTransition |
LONG |
ReadOnly |
|
ExpirationTime |
BACnetDateTime |
STRING |
ReadOnly |
|
InitialTimeout |
Unsigned |
LONG |
Read/Write |
|
DefaultTimeout |
Unsigned |
LONG |
Read/Write |
|
MaxPresValue |
Unsigned |
LONG |
Read/Write |
|
Resolution |
Unsigned |
LONG |
Read/Write |
|
StateChangeValues.1..7 |
BACnetARRAY[7] of BACnetTimerStateChangeValue |
STRING |
ReadOnly |
|
ObjPropRefList |
BACnetLIST of BACnetDeviceObjectPropertyReference |
(See ListOf DeviceObjectProperty Reference sub-properties at Schedule object ) |
ReadOnly |
|
PriorityForWriting |
Unsigned(1...16) |
LONG |
Read/Write |
|
EventDetectionEnable |
Boolean |
DIGITAL |
Read/Write |
|
NotificationClass |
Unsigned |
LONG |
Read/Write |
|
TimeDelay |
Unsigned |
LONG |
Read/Write |
|
TimeDelayNormal |
Unsigned |
LONG |
Read/Write |
|
AlarmValues List of Unsigned property represented as a string of integers separated by a comma |
BACnetLIST of BACnetTimerState |
STRING |
Read/Write |
|
EventEnable BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows: Bit 0 – to off normal Bit 1 – to fault Bit 2 – to normal |
BACnetEventTransitionBits |
LONG |
Read/Write |
|
AckedTransitions BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows: Bit 0 – to off normal Bit 1 – to fault Bit 2 – to normal |
BACnetEventTransitionBits |
LONG |
ReadOnly |
|
NotifyType |
BACnetNotifyType |
LONG |
Read/Write |
|
EventTimeStamps. EventTimeStamps.ToFault EventTimeStamps.ToNormal BACnetTimeStamp properties represented as a string in Australian time format |
BACnetARRAY[3] of BACnetTimeStamp |
STRING |
ReadOnly |
|
EventMessageTexts. EventMessageTexts.ToFault EventMessageTexts. |
BACnetARRAY[3] of CharacterString |
STRING |
ReadOnly |
|
EventMessageTextsConfig. EventMessageTextsConfig. EventMessageTextsConfig. |
BACnetARRAY[3] of CharacterString |
STRING |
ReadOnly |
|
EventAlgorithmInhibitRef. EventAlgorithmInhibitRef. EventAlgorithmInhibitRef. |
BACnetObjectPropertyReference |
LONG |
ReadOnly |
|
EventAlgorithmInhibit |
Boolean |
DIGITAL |
Read/Write |
|
ReliabilityEvaluationInhibit |
Boolean |
DIGITAL |
Read/Write |
|
Tags List of Name Values will be represented as a string separated by a comma and Name , Values are separated by ';' |
BACnetARRAY[N] of BACnetNameValue |
STRING |
ReadOnly |
|
ProfileLocation |
CharacterString |
STRING |
Read/Write |
|
ProfileName |
CharacterString |
STRING |
ReadOnly |