Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

Timer Objects

  • Last UpdatedJul 07, 2025
  • 2 minute read

Property Mnemonic

BACnet Data Type

Plant SCADA Data Type

Access

ObjectIdentifier

BACnetObjectIdentifier

LONG

ReadOnly

ObjectName

CharacterString

STRING

ReadOnly

ObjectType

BACnetObjectType

LONG

ReadOnly

Description

CharacterString

STRING

Read/Write

PresentValue

Unsigned

LONG

Read/Write

StatusFlags

BACnetStatusFlags

STRING

ReadOnly

EventState

BACnetEventState

LONG

ReadOnly

Reliability

BACnetReliability

LONG

Read/Write

OutOfService

Boolean

DIGITAL

Read/Write

TimerState

BACnetTimerState

LONG

ReadOnly

TimerRunning

Boolean

DIGITAL

Read/Write

UpdateTime

BACnetDateTime

STRING

ReadOnly

LastStateChange

BACnetTimerTransition

LONG

ReadOnly

ExpirationTime

BACnetDateTime

STRING

ReadOnly

InitialTimeout

Unsigned

LONG

Read/Write

DefaultTimeout

Unsigned

LONG

Read/Write

MaxPresValue

Unsigned

LONG

Read/Write

Resolution

Unsigned

LONG

Read/Write

StateChangeValues.1..7

BACnetARRAY[7] of BACnetTimerStateChangeValue

STRING

ReadOnly

ObjPropRefList

BACnetLIST of BACnetDeviceObjectPropertyReference

(See ListOf DeviceObjectProperty Reference sub-properties at Schedule object )

ReadOnly

PriorityForWriting

Unsigned(1...16)

LONG

Read/Write

EventDetectionEnable

Boolean

DIGITAL

Read/Write

NotificationClass

Unsigned

LONG

Read/Write

TimeDelay

Unsigned

LONG

Read/Write

TimeDelayNormal

Unsigned

LONG

Read/Write

AlarmValues

List of Unsigned property represented as a string of integers separated by a comma

BACnetLIST of BACnetTimerState

STRING

Read/Write

EventEnable

BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows:

Bit 0 – to off normal

Bit 1 – to fault

Bit 2 – to normal

BACnetEventTransitionBits

LONG

Read/Write

AckedTransitions

BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows:

Bit 0 – to off normal

Bit 1 – to fault

Bit 2 – to normal

BACnetEventTransitionBits

LONG

ReadOnly

NotifyType

BACnetNotifyType

LONG

Read/Write

EventTimeStamps.
ToOffNormal

EventTimeStamps.ToFault

EventTimeStamps.ToNormal

BACnetTimeStamp properties represented as a string in Australian time format

BACnetARRAY[3] of BACnetTimeStamp

STRING

ReadOnly

EventMessageTexts.
ToOffNormal

EventMessageTexts.ToFault

EventMessageTexts.
ToNormal

BACnetARRAY[3] of CharacterString

STRING

ReadOnly

EventMessageTextsConfig.
ToOffNormal

EventMessageTextsConfig.
ToFault

EventMessageTextsConfig.
ToNormal

BACnetARRAY[3] of CharacterString

STRING

ReadOnly

EventAlgorithmInhibitRef.
ObjectIdentifier

EventAlgorithmInhibitRef.
PropertyIdentifier

EventAlgorithmInhibitRef.
PropertyArrayIndex

BACnetObjectPropertyReference

LONG

ReadOnly

EventAlgorithmInhibit

Boolean

DIGITAL

Read/Write

ReliabilityEvaluationInhibit

Boolean

DIGITAL

Read/Write

Tags

List of Name Values will be represented as a string separated by a comma and Name , Values are separated by ';'

BACnetARRAY[N] of BACnetNameValue

STRING

ReadOnly

ProfileLocation

CharacterString

STRING

Read/Write

ProfileName

CharacterString

STRING

ReadOnly

TitleResults for “How to create a CRG?”Also Available in