DDE Shares
- Last UpdatedJul 13, 2023
- 1 minute read
There are three types of DDE shares: old style, new style, and static. Plant SCADA only supports the static type. The names of static shares follow the convention
<ShareName>$
so to set up a Plant SCADA server computer as a Network DDE share, use the name "Citect$" as the sharename on that computer. To expose the Plant SCADA runtime variable tag database for suitable DDE linking, use the word "Variable" as the DDE Share Topic name.
Note: The trailing dollar sign ($) is necessary as part of the DDE share name syntax.
To create a DDE share:
-
In the DDE Shares dialog, click Add a Share. The DDE Shares Properties dialog appears. Verify that the fields are blank, or unchecked, except for the Grant access to every item radio button which needs to be checked.
-
Click Permissions. The DDE Share Name Permissions dialog appears.
-
Read and Link is the default permission setting. If you want to write data to the DDE Share application, change the permission to Full Control.
-
Click OK.
-
Click OK to save the Share, and return to the DDE Shares dialog.