[Trend]MaxRdnSamples

  • Last UpdatedJul 19, 2023
  • 1 minute read

Determines the maximum number of samples in a single redundancy backfilling request for a particular trend. Increasing the value of this parameter will cause trend redundancy requests to be larger which may speed up trend redundancy backfilling, but at the potential cost of making the trend server less responsive to display client requests during redundancy synchronisation. Decreasing the value of this parameter will cause trend redundancy requests to be smaller, potentially allowing display client trend requests to be responded to faster during redundancy synchronisation, but this may slow down trend redundancy synchronisation.

Allowable Values:

1 to 32767

Default Value:

500

See Also

Trend Parameters