AVEVA™ Plant SCADA

ABTCP Driver Specific Errors

  • Last UpdatedOct 27, 2021
  • 4 minute read

When a hardware error is detected, Plant SCADA generates an alarm, and displays the alarm on the hardware alarm page (in the alarm description of the hardware alarm). To see the error number, make sure you have Alarm Category 255 defined with a display format that includes {ErrDesc,15} {ErrPage,10}.

There are a number of generic errors that are common to all protocols. In some cases, only the generic error is available, though often both the generic error and a specific error are given.

The following errors, listed in (hexadecimal) sequence, are specific to this protocol. Plant SCADA displays the error number and description for common protocol-specific errors. Uncommon errors are not contained in the error database, in which case will only display the error number.

You may require additional information to enable you to rectify an error. This information should be detailed in the documentation that accompanied the I/O Device (or network). If, after reviewing all documentation, you cannot rectify an error, contact Technical Support.

0x10100PLC out of buffers

Check the PLC configuration.

0x10200 PLC is not online

Check that the PLC is online.

0x10300 Duplicated token holder detected

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x10400 Local port is disconnected

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x11000 Illegal command or format

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x12000 Host will not communicate

Check the project configuration and PLC configuration.

0x13000 PLC hardware fault

Address this problem at the PLC.

0x14000 Host hardware fault

Your hardware may not be functional. If this is persistent try using duplicate hardware.

0x15000 Illegal data table address

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x16000 PLC is write protected

Change the configuration of your PLC (if desired).

0x17000 Processor is in program mode

Switch your processor to RUN mode (if desired).

0x18000 Compatibility file is missing

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x19000 PLC cannot buffer command

If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1B000 PLC problem due to download

If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1F001Error converting block address

If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1F002 Insufficient levels of address

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x1F003 Too many levels in address

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x1F004 Symbol not found

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x1F005 Symbol is of improper format

Check the project configuration and PLC configuration.

0x1F006 Invalid address

The data requested by is not configured in the PLC. Check the project configuration and PLC configuration.

0x1F007 File is of wrong size

The data requested by is out of range or is not defined in the I/O Device. Check the project configuration and PLC configuration.

0x1F008 Changed situation since start

If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1F009 File is too large

The data requested by is out of range or is not defined in the I/O Device. Check the project configuration and PLC configuration.

0x1F00A Word and count too large

The data requested by is out of range. Check the project configuration and PLC configuration.

0x1F00B Access denied

The PLC is denying access. If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1F00C Resource unavailable

Check the project configuration and PLC configuration. If this error occurs by itself and is persistent, contact Technical Support for this product.

0x1F00D File of wrong size

The data requested by is out of range or is not defined in the I/O Device. Check the project configuration and PLC configuration.

0x1F00E Shutdown cannot be executed

If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1F00F File is too large

The data requested by is not configured in the PLC. Check the project configuration and PLC configuration.

0x1F010 Histogram overflow

If this error is persistent, check the PLC configuration and refer to your PLC documentation.

0x1F011Illegal data type

The data requested by is not configured in the PLC. Check the project configuration and PLC configuration.

0x1F012 Bad parameter

Check the project configuration and PLC configuration.

0x1F013 Data table deleted

If this error occurs by itself and is persistent, contact Technical Support for this product.

0x1F0FF *

EXT STS error code.

0x1FF00*

Local STS error code.

0x1F000 *

Remote STS error code.