Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

PageListDisplay

  • Last UpdatedJul 18, 2023
  • 1 minute read

Recalls (displays) a page at the specific index in the page list of current window, and moves the current index to the page. When a page is recalled, the original parameters (such as cluster context, supergenie associations, PageTask arguments if applicable) used to display the page will be restored.

(See the Citect.ini parameter [Page]MaxList.

Syntax

PageListDisplay(INT index)

Index

Index to the page list (valid range 0 to list size minus 1)

Return Value

0 (zero) if the page is successfully displayed, otherwise an error is returned.

PageListCount, PageListCurrent, PageListInfo, PageListDelete

Example


INT count;
INT index;
INT error;
STRING PageName;

// While 4 entries will be added to page history, only 3 unique pages will be added to page list
PageDisplay(Page1);
PageDisplay(Page2);
PageDisplay(Page1);
PageDisplay(Page3);

// iterate the pages in the list
count=PageListCount() //count=3
PageName=PageListInfo(0,0); //PageName=Page1
PageName=PageListInfo(1,0); //PageName=Page2
PageName=PageListInfo(2,0); //PageName=Page3
index=PageListCurrent(); //index=2,as Page3 is currently displayed
pageName=PageListInfo(index,0); //PageName=Page3
error-PageListDisplay(1); //recall Page2, error=0
index=PageListCurrent(); //index=1, as current index is moved as part of the recall
PageName=PageInfo(0); //PageName=Page2 as it becomes the current page
error=PageListDelete(index); //remove current page, i.e. Page2, error=0
PageName=PageInfo(0); //PageName=Page3, next page in the list is displayed
index=PageListCurrent(); //index=1, current index is not changed while the list is reduced
count=PageListCount(); //count=2, only 2 pages left in the list

See Also

Page Functions

In This Topic
Related Links