[Alarm.<ClusterName>.<ServerName>]Priority
- Last UpdatedJul 19, 2023
- 1 minute read
This setting is used to specify the client sub system’s priority for the connection to this specific server. The client sub system will connect to, or switch over to, any available server that has the highest priority (lowest number). If the priorities for multiple servers are set to the same value, the client sub system will only switch on a loss of the currently active connection.
This is the default operation to provide the same behavior as in versions of the product prior to v7.20.
To disable (not allow) the client to connect to the server use [Alarm.<ClusterName>.<ServerName>]DisableConnection.
Note: This parameter needs to be applied to a specific alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.
Allowable Values:
1 to 32767.
Default Value:
1