Loop Objects

  • Last UpdatedJul 07, 2025
  • 2 minute read

Property Mnemonic

BACnet Data Type

Plant SCADA Data Type

Access

AckedTransitions

BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows:

Bit 0 – to off normal

Bit 1 – to fault

Bit 2 – to normal

BACnetEventTransitionBits

LONG

Read Only

Action

BACnetAction

LONG

Read/Write

OutOfService

Boolean

DIGITAL

Read/Write

ReliabilityEvaluationInhibit

Boolean

DIGITAL

Read/Write

EventAlgorithmInhibit

Boolean

DIGITAL

Read/Write

PresentValue

Real

REAL

Read/Write

ObjectIdentifier

BACnetObjectIdentifier

LONG

Read Only

ObjectType

BACnetObjectType

LONG

Read Only

EventState

BACnetEventState

LONG

Read Only

EventDetectionEnable

Boolean

LONG

Read/Write

UpdateInterval

Unsigned

LONG

Read/Write

PriorityForWriting

Unsigned

LONG

Read/Write

Description

CharacterString

STRING

Read/Write

StatusFlags

BACnetStatusFlags

STRING

Read Only

ObjectName

CharacterString

STRING

Read Only

ErrorLimit

Real

REAL

Read/Write

ControlledVariableUnits

BACnetEngineeringUnits

LONG

Read/Write

ControlledVariableValue

Real

REAL

Read/Write

DerivativeConstantUnits

BACnetEngineeringUnits

LONG

Read/Write

EventMessageTexts.ToOffNormal

EventMessageTexts.ToFault

EventMessageTexts.ToNormal

BACnetARRAY[3] of
CharacterString

STRING

Read/Write

EventMessageTextsConfig
.ToOffNormal

EventMessageTextsConfig
.ToFault

EventMessageTextsConfig
.ToNormal

BACnetARRAY[3] of
CharacterString

STRING

Read/Write

DerivativeConstant

Real

REAL

Read/Write

Deadband

Real

REAL

Read/Write

TimeDelay

Unsigned

LONG

Read/Write

TimeDelayNormal

Unsigned

LONG

Read/Write

EventEnable

BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows:

Bit 0 – to off normal

Bit 1 – to fault

Bit 2 – to normal

BACnetEventTransitionBits

LONG

Read/Write

EventTimeStamps.ToOffNormal

EventTimeStamps.ToFault

EventTimeStamps.ToNormal

BACnetTimeStamp properties represented as a string in Australian time format

BACnetARRAY[3] of
BACnetTimeStamp

STRING

Read Only

Reliability

BACnetReliability

LONG

Read/Write

Setpoint

Real

REAL

Read/Write

MaximumOutput

Real

REAL

Read/Write

MinimumOutput

Real

REAL

Read/Write

ProportionalConstant

Real

REAL

Read/Write

LowDiffLimit

BACnetOptionalReal

REAL

Read/Write

ProportionalConstantUnits

BACnetEngineeringUnits

LONG

Read/Write

IntegralConstant

Real

REAL

Read/Write

IntegralConstantUnits

BACnetEngineeringUnits

LONG

Read/Write

COVIncrement

Real

REAL

Read/Write

NotificationClass

Unsigned

LONG

Read/Write

NotifyType

BACnetNotifyType

LONG

Read/Write

ProfileName

CharacterString

STRING

Read Only

ProfileLocation

CharacterString

STRING

Read/Write

Bias

Real

REAL

Read/Write

SetpointReference.ObjectIdentifier

SetpointReference.PropertyIdentifier

SetpointReference.PropertyArrayIndex

BACnetObjectPropertyReference

LONG

Read Only

SetpointReference.PropPresent

Boolean

DIGITAL

Read Only

ControlledVariableReference
.ObjectIdentifier

ControlledVariableReference
.PropertyIdentifier

ControlledVariableReference
.PropertyArrayIndex

BACnetObjectPropertyReference

LONG

Read Only

ManipulatedVariableReference
.ObjectIdentifier

ManipulatedVariableReference
.PropertyIdentifier

ManipulatedVariableReference
.PropertyArrayIndex

BACnetObjectPropertyReference

LONG

Read Only

OutputUnits

BACnetEngineeringUnits

LONG

Read/Write

PropertyList.1..63

BACnetARRAY[N] of BACnetPropertyIdentifier

LONG

Read Only

Tags

List of Name Values will be represented as a string separated by a comma and Name , Values are separated by ';'

BACnetARRAY[N] of BACnetNameValue

STRING

Read Only