Loop Objects
- Last UpdatedJul 07, 2025
- 2 minute read
|
Property Mnemonic |
BACnet Data Type |
Plant SCADA Data Type |
Access |
|
AckedTransitions BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows: Bit 0 – to off normal Bit 1 – to fault Bit 2 – to normal |
BACnetEventTransitionBits |
LONG |
Read Only |
|
Action |
BACnetAction |
LONG |
Read/Write |
|
OutOfService |
Boolean |
DIGITAL |
Read/Write |
|
ReliabilityEvaluationInhibit |
Boolean |
DIGITAL |
Read/Write |
|
EventAlgorithmInhibit |
Boolean |
DIGITAL |
Read/Write |
|
PresentValue |
Real |
REAL |
Read/Write |
|
ObjectIdentifier |
BACnetObjectIdentifier |
LONG |
Read Only |
|
ObjectType |
BACnetObjectType |
LONG |
Read Only |
|
EventState |
BACnetEventState |
LONG |
Read Only |
|
EventDetectionEnable |
Boolean |
LONG |
Read/Write |
|
UpdateInterval |
Unsigned |
LONG |
Read/Write |
|
PriorityForWriting |
Unsigned |
LONG |
Read/Write |
|
Description |
CharacterString |
STRING |
Read/Write |
|
StatusFlags |
BACnetStatusFlags |
STRING |
Read Only |
|
ObjectName |
CharacterString |
STRING |
Read Only |
|
ErrorLimit |
Real |
REAL |
Read/Write |
|
ControlledVariableUnits |
BACnetEngineeringUnits |
LONG |
Read/Write |
|
ControlledVariableValue |
Real |
REAL |
Read/Write |
|
DerivativeConstantUnits |
BACnetEngineeringUnits |
LONG |
Read/Write |
|
EventMessageTexts.ToOffNormal EventMessageTexts.ToFault EventMessageTexts.ToNormal |
BACnetARRAY[3] of |
STRING |
Read/Write |
|
EventMessageTextsConfig EventMessageTextsConfig EventMessageTextsConfig |
BACnetARRAY[3] of |
STRING |
Read/Write |
|
DerivativeConstant |
Real |
REAL |
Read/Write |
|
Deadband |
Real |
REAL |
Read/Write |
|
TimeDelay |
Unsigned |
LONG |
Read/Write |
|
TimeDelayNormal |
Unsigned |
LONG |
Read/Write |
|
EventEnable BACnetEventTransitionBits represented as a long integer. Bits are stored in the integer as follows: Bit 0 – to off normal Bit 1 – to fault Bit 2 – to normal |
BACnetEventTransitionBits |
LONG |
Read/Write |
|
EventTimeStamps.ToOffNormal EventTimeStamps.ToFault EventTimeStamps.ToNormal BACnetTimeStamp properties represented as a string in Australian time format |
BACnetARRAY[3] of |
STRING |
Read Only |
|
Reliability |
BACnetReliability |
LONG |
Read/Write |
|
Setpoint |
Real |
REAL |
Read/Write |
|
MaximumOutput |
Real |
REAL |
Read/Write |
|
MinimumOutput |
Real |
REAL |
Read/Write |
|
ProportionalConstant |
Real |
REAL |
Read/Write |
|
LowDiffLimit |
BACnetOptionalReal |
REAL |
Read/Write |
|
ProportionalConstantUnits |
BACnetEngineeringUnits |
LONG |
Read/Write |
|
IntegralConstant |
Real |
REAL |
Read/Write |
|
IntegralConstantUnits |
BACnetEngineeringUnits |
LONG |
Read/Write |
|
COVIncrement |
Real |
REAL |
Read/Write |
|
NotificationClass |
Unsigned |
LONG |
Read/Write |
|
NotifyType |
BACnetNotifyType |
LONG |
Read/Write |
|
ProfileName |
CharacterString |
STRING |
Read Only |
|
ProfileLocation |
CharacterString |
STRING |
Read/Write |
|
Bias |
Real |
REAL |
Read/Write |
|
SetpointReference.ObjectIdentifier SetpointReference.PropertyIdentifier SetpointReference.PropertyArrayIndex |
BACnetObjectPropertyReference |
LONG |
Read Only |
|
SetpointReference.PropPresent |
Boolean |
DIGITAL |
Read Only |
|
ControlledVariableReference ControlledVariableReference ControlledVariableReference |
BACnetObjectPropertyReference |
LONG |
Read Only |
|
ManipulatedVariableReference ManipulatedVariableReference ManipulatedVariableReference |
BACnetObjectPropertyReference |
LONG |
Read Only |
|
OutputUnits |
BACnetEngineeringUnits |
LONG |
Read/Write |
|
PropertyList.1..63 |
BACnetARRAY[N] of BACnetPropertyIdentifier |
LONG |
Read Only |
|
Tags List of Name Values will be represented as a string separated by a comma and Name , Values are separated by ';' |
BACnetARRAY[N] of BACnetNameValue |
STRING |
Read Only |