Modicon 584 PLCs - Communication Settings

  • Last UpdatedDec 06, 2021
  • 2 minute read

To establish communication with a device, configure the Boards, Port and I/O Device in Plant SCADA Studio's Topology activity. If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to manually configure these, use the settings outlined below.

Board Settings

Typically, you would use a serial board or COM port for this communication. Refer to the instructions for setting up and using COM ports or serial boards. Or complete the Board settings with the following specific information.

Field

Value

Board Type

If using a serial board or COM port, enter COMx.

Address

If using a serial board or COM port, enter 0.

I/O Port

Leave this field blank.

Interrupt

Leave this field blank.

Special Options

Leave this field blank.

Port Settings

Complete the Port settings with the following specific information.

Field

Value

Port Number

This value matches the COM port number. This number is defined in the Ports section of the Control Panel.

Baud Rate

This value matches the setting of the unit - 19200.

Data Bits

Enter 8.

Stop Bits

Enter 1.

Parity

This value matches the setting of the unit - EVEN_P.

Special Options

You may want to use the special options for the COMx Driver if you are using a modem (or similar) and want the driver to perform differently.

For more information, see the topic COMx Driver Special Options Reference in the Communicating with I/O Devices chapter of the main help.

I/O Device Settings

Complete the I/O Device settings with the following specific information.

Field

Value

I/O Device Address

The PLC station number configured on the PLC. Try 1 to 10.

1 specifies station number 1.

9 specifies station number 9.

I/O Device Protocol

Enter MODBUS if you want to use the Modbus RTU (binary) protocol.

Enter MODBUSA if you want to use the Modbus ASCII protocol.

(See the topic Protocol Variants to determine if a non-standard protocol variant is required.)