[CtEdit]Run
- Last UpdatedFeb 02, 2024
- 2 minute read
The directory where the runtime project is located. If you run the project from Plant SCADA Studio, Graphics Builder, or Cicode Editor, this parameter will be automatically set to the name of the current project. If you want to run a project independently of these applications, you will need to set this parameter manually. It is recommended that the directory chosen should be a sub directory of the ..\Plant SCADA\User directory.
Note: Do not use the [CtEdit]Run and [CtEdit]Copy parameters if you intend to use Plant SCADA's Deployment functionality.
|
|
|
UNINTENDED EQUIPMENT OPERATION Restart the client process if the hardware alarm "Cicode library timestamp differs" is raised after a page is opened. A hardware alarm of "Cicode library timestamp differs" will be raised if the Cicode library used by a page has a different timestamp from the one in memory. The timestamps will be different if the project has been fully recompiled, the project has been incrementally recompiled after the page has been modified, or if the project has been incrementally recompiled after any Cicode has been modified. Failure to follow these instructions can result in death, serious injury, or equipment damage. |
Note:
1. For RUN/COPY (deployment) setup, use [Alarm]UseConfigLimits=0 so that the alarm properties are not persisted to the DBF/RDB files. If not the
RDB files will be over written the next time they are accessed by the system.
2. If you have set a COPY directory (using the [CtEdit]Copy parameter), any changes made and compiled in that directory will be automatically
copied to the RUN directory. Any file with a name that matches one of the files changed
in the COPY directory will be overwritten during this process. This copy only occurs
when the files are accessed at runtime.
Allowable Values:
Any valid directory under the ..\Plant SCADA\User directory.
Default Value:
No default value.
Note: If running a <profilename>.ini, the value for this parameter will always be taken from the local Citect.Ini file.
For additional information, refer to the topic Client Side Online Changes in the main Plant SCADA documentation.
