Schedule Integration
- Last UpdatedJul 13, 2023
- 1 minute read
Scheduler now supports the integration of schedules that are configured on a BACNet device. Locally configured schedule items on a BACNet device can be imported into Plant SCADA. You can also view and modify schedule-object and calendar-object properties on a BACNet device at runtime.
Schedule integration is enabled via the following process:
-
A BACnet I/O device is configured in Plant SCADA Studio and connected to Plant SCADA via the BACNET driver.
-
Variable tags and equipment definitions that represent the device's schedule and calendar objects are configured on the I/O server through tag import.
-
The reports server subscribes to the tags on the I/O server and generates schedule entries in Scheduler.
-
Any changes to the schedule entries are written back to the BACnet device via the I/O server.