Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

Impact of a Server Reload on Historical Records

  • Last UpdatedJul 18, 2023
  • 2 minute read

The following sections detail the effects on the history of reloaded Alarm, Trend and Report records. This is dependent on which fields have changed.

  • A ‘Yes’ in the New Alarm column indicates changes to that field will make a new alarm and delete the old one and therefore the history is not kept.

  • A ‘Yes’ in the Invalid History column means changes to that field will make the history of that record invalid.

Alarm Servers

Common Alarm fields

Field Name

New Alarm

Invalid History

Alarm Tag

Yes

No

Cluster Name

Yes

No

Alarm Description

No

No

Alarm Category

No

No

Help

No

No

Delay

No

No

Comment

No

No

Privilege

No

No

Area

No

No

Custom 1..8

No

No

Paging

No

No

Paging Group

No

No

Analog and Time Stamped Analog Alarm fields

Field Name

New Alarm

Invalid History

Variable Tag

No

Yes

High High

No

Yes

High

No

Yes

Low Low

No

Yes

Low

No

Yes

SetPoint

No

Yes

Deviation

No

Yes

High High Delay

No

No

High Delay

No

No

Low Low Delay

No

No

Low Delay

No

No

Deviation Delay

No

No

Rate

No

Yes

Deadband

No

Yes

Format

No

No

Digital and Time Stamped Digital Alarm fields

Field Name

New Alarm

Invalid History

Variable Tag A

No

Yes

Variable Tag B

No

Yes

Time Stamped Alarm fields

Field Name

New Alarm

Invalid History

Variable Tag

No

Yes

Timer

No

Yes

Advanced Alarm fields

Field Name

New Alarm

Invalid History

Expression

No

Yes

Multi-Digital Alarm fields

Field Name

New Alarm

Invalid History

Variable Tag A

No

Yes

Variable Tag B

No

Yes

Variable Tag C

No

Yes

Realarm

No

Yes

On Function

No

Yes

Off Function

No

Yes

State

No

Yes

State Description

No

Yes

Trend Servers

Changes to the following properties of trends make existing trend files invalid and result in the creation of a new trend file (renaming the old one for backup):

  • Sample Period

  • Type

  • Storage Method

  • No of Files

  • Time (File)

  • Period (File)

Changing the scale of a tag will make the trend history invalid.

Effect of reload on a modified Trend:

Field Name

New Alarm

Invalid History

Trend Tag Name

Yes

No

Cluster Name

Yes

No

Expression

No

Yes

Trigger

No

Yes

Comment

No

No

Privilege

No

No

Area

No

No

Eng Units

No

No

Format

No

No

Report Servers

Effect of reload on a modified Report:

Field Name

New Alarm

Invalid History

Report Name

Yes

No

Cluster Name

Yes

No

Time

No

Yes

Period

No

Yes

Trigger

No

No

Report File Format

No

No

Output Device

No

No

Privilege

No

No

Area

No

No

Accumulators

Effect of reload on a modified Accumulator:

Field Name

New Alarm

Invalid History

Name

Yes

No

Cluster Name

Yes

No

Trigger

No

Yes

Run Time

No

Yes

No. of Starts

No

No

Totaliser Inc

No

No

Totaliser

No

No

Comment

No

No

Privilege

No

No

Area

Yes

No

In This Topic