Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

Counter Data File

  • Last UpdatedMar 06, 2024
  • 1 minute read

Plant SCADA Type

Tag Address Rule

Allowable Value Ranges

INT

Cf:e.s

Cf:e.PRE/0

Cf:e.ACC/0

f - file number: 5,[9-255]

e - element number:[0-255]

s - sub-element number: [0-2]

"/0" is optional

DIGITAL

Cf:e/b

Cf:e/UA

Cf:e/UN

Cf:e/OV

Cf:e/DN

Cf:e/CD

Cf:e/CU

f - file number: 5,[9-255]

e - element number:[0-255]

b - bit number: [0-15]

Examples

Examples

Meaning

C5:1.0

Counter data file 5, element 1, sub-element 0

C5:1.PRE

Counter data file 5, element 1, sub-element 1 (equivalent to PRE)

C5:1.ACC/0

Counter data file 5, element 1, sub-element 2 (equivalent to ACC)

C5:2/11

Counter data file 5, element 2, bit number 11

C5:2/UN

Counter data file 5, element 2, bit number 11 (equivalent to UN)