[Alarm]MemoryWarningLimit

  • Last UpdatedJul 19, 2023
  • 1 minute read

Value in Mb, of the threshold of the alarm server memory.

If the threshold is reached a hardware alarm will be raised which will be visible on all clients connected to that cluster, whether they are connected to the standby or primary alarm servers.

To turn off the hardware alarm change the MemoryWarningLimit to 0.

The hardware alarm message is "Memory above safe limit".

Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.

Allowable Values:

0 to 2147483647 (Mb)

Default Value:

4000 (4Gb)