Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

Time Synchronization Parameters

  • Last UpdatedAug 04, 2025
  • 1 minute read

warning2

UNINTENDED EQUIPMENT OPERATION

Do not change these protocol parameters, except on the advice of Technical Support for this product.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Note: At times during the life cycle of a driver, circumstances may call for the creation of specific citect.ini parameters that remain undocumented. Always seek the advice of Technical Support regarding the possible implementation of undocumented parameters before you make any changes to a citect.ini file.

[IEC870IP] Parameter

Description

Allowable Values

Default Value

TimeSyncOnInit

Determines whether or not the time is set for a device as it comes online.

Note: You can set this parameter for every device connected to a specific port. See Port-specific Parameters.

0 - do not set the time for a device as it comes online.

1 - set the time for a device as it comes online.

1

TimeSyncPollTimeSec

Determines how often the time is set for a device (in seconds).

0-32767
(seconds)

1800

TimeSyncDelayAcquire

Determines if a delay acquisition command is sent when a time synchronization response is received.

Note: You can set this parameter for every device connected to a specific port. See Port-specific Parameters.

0 - do not send a delay acquisition command.

1 - send a delay acquisition command.

0