The Citect.ini file contains the following report parameters:

  • [Report]ComBreak - Determines whether reports that are triggered from the I/O devices are run if a communication break exists.

  • [Report]Debug - Enables trace logging messages.

  • [Report]Disable - Enables/disables the Reports Server.

  • [Report]HeartBeat - Determines whether the Primary and Redundant Reports Servers send out heartbeat signals to each other.

  • [Report]HeartBeatTime - Determines the period at which heartbeat signals are sent out by the Primary Reports Server. Also determines the period that the Redundant Reports Server will wait for a response (before assuming control of reports) after sending a heartbeat signal to the Primary Reports Server.

  • [Report]InhibitEvent - Inhibits event-type reports on startup.

  • [Report]Primary - Obsolete in version 7.0.

  • [Report]Process - Obsolete in version 7.0.

  • [Report]RtfRollOver - Determines whether an RTF report will save to a new file, or append to an existing file.

  • [Report]RunStandby - Enables or disables tandem processing of reports.

  • [Report]Server - Obsolete in version 7.0.

  • [Report]Startup - The report to run when Plant SCADA starts up.

  • [Report]TxtRollOver - Determines whether a text report will save to a new file, or append to an existing file.

  • [Report]WatchTime - The period at which Plant SCADA checks for reports to run.