Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Plant SCADA

[Trend]FileCreationWriteSize

  • Last UpdatedJul 19, 2023
  • 1 minute read

Controls the rate at which trend files are initialised (whether created at startup or runtime). Optimal performance is achieved with values of 327680 bytes or lower. File writes larger than this may be batched in chunks of 65536 bytes, reducing the performance benefit. Environmental factors may also alter this threshold.

Allowable Values:

1 to 2147483647

Default Value:

16384

See Also

Trend Parameters