AlmSummaryClear

  • Last UpdatedJul 18, 2023
  • 1 minute read

The AlmSummaryClear function clears the latched alarm at the current cursor position in an active data browse session. A latched alarm is an alarm which is OFF and acknowledged when [Alarm]AckHold is set to 1. The function does nothing if the alarm summary entry at the cursor is not linked to a latched alarm.

This function is a non-blocking function. It does not block the calling Cicode task.

Syntax

INT AlmSummaryClear(LONG Session)

Session:

The handle to a browse session previously returned by a AlmSummaryOpen call.

Return Value

0 (zero) if the alarm browse session exists, otherwise an error code is returned.

AlmSummaryAck, AlmSummaryClose, AlmSummaryDelete, AlmSummaryDeleteAll, AlmSummaryDisable, AlmSummaryEnable, AlmSummaryGetField,AlmSummaryLast, AlmSummaryNext, AlmSummaryOpen, AlmSummaryPrev, AlmSummaryNumRecords