AVEVA™ Plant SCADA

Communications Settings

  • Last UpdatedAug 04, 2025
  • 2 minute read

To establish communication with a device, the associated Board, Port and I/O Device need to be correctly configured in Plant SCADA Studio's Topology activity.

If you use the Express Communications Wizard to connect to a device, these settings will be automatically configured for you. However, if you need to configure the settings manually, use the values outlined below.

Board settings

The Boards view lists boards used in the Plant SCADA project. Each board record defines a separate board within the project.

The IEC870IP driver is a board-level driver, which means it requires a single board configured for each I/O server.

Field

Value

Board Name

Any user-defined name (e.g. "Board1")

Board Type

TCP/IP

Address

0 (zero)

I/O Port

Leave this field blank

Interrupt

Leave this field blank

Special Options

Leave this field blank

Comment

Any useful comment (not required by the driver)

Port settings

The Ports view lists the ports used in the Plant SCADA project. Each port record defines a separate port within the project.

A separate port should be created for each IEC 870-5-104 device.

Field

Value

Port Name

Any user-defined name (e.g. "Port1")

Port Number

The default port number for the IEC 870-5-104 protocol is 2404.

Board Name

Refers to the board defined in the Boards form

Baud Rate

Leave this field blank

Data Bits

Leave this field blank

Stop Bits

Leave this field blank

Parity

Leave this field blank

Special Options

Use the address for the IEC 870-5-104 device using the following format:

—I<device IP address> —P<port number> —<T (TCP)>

For example:
—I192.1.1.182—P2404 —T

The default port number for the IEC 870-5-104 protocol is 2404

Comment

Any useful comment (not required by the driver)

I/O Device settings

The I/O Devices view lists I/O devices used in the Plant SCADA project. Each device record defines a device within the project.

A Plant SCADA I/O device represents a single IEC 870-5-104 device.

Field

Value

Name

Any user-defined name (e.g. "IODevice1")

Number

I/O device number needs to be unique for each I/O device,
but identical for redundant devices.

Address

The address to use for an IEC 870-5-104 device is the common ADSU address. This value is configured on the device and will be a number between 1 and 65535.

Protocol

IEC870IP

Port Name

Refers to the port defined in the Ports form

Comment

Any useful comment. This field is user defined and not required by the driver