Returns the status of the specified SPC alarm. This function is used to configure SPC alarms, by defining alarms with this trigger in Advanced Alarms.

This function can only be used if the Alarm Server is on the current machine. When the Alarm Server is not in the calling process, this function will become blocking and cannot be called from a foreground task. In this case, the return value will be undefined and a Cicode hardware alarm will be raised.

Syntax

SPCAlarms(sSPCTag, AlarmType)

sSPCTag:

The SPC Tag name as defined in SPC Tags.

AlarmType:

The description of the alarm type. The following types are valid:

XFreak

XOutsideCL

XAboveUCL

XBelowLCL

XOutsideWL

XGradualUp

XGradualDown

XUpTrend

XDownTrend

XErratic

XStratification

XMixture

ROutsideCL

RAboveUCL

RBelowLCL

Return Value

Alarm status, ON (1) or OFF (0).

AlarmAck

Example

Advanced Alarm

Alarm Tag

Feed_SPC_XBLCL

Alarm Desc

Process mean below LCL

Expression

SPCAlarms("Feed_SPC", XBelowLCL)

Comment

Trigger an alarm when XBelowLCL condition becomes true.

Advanced Alarm

Alarm Tag

Temp_SPC_GRADUP

Alarm Desc

Mean is drifting up

Expression

SPCAlarms("Temp_SPC", XGradualUp)

Comment

Trigger an alarm if mean drifts up.