[Alarm]SummaryTimeoutTolerance
- Last UpdatedJul 19, 2023
- 1 minute read
The length of time from timeout after which an alarm summary entry is committed to Summary Device regardless the fact that Off Time is not set.
The purpose of this parameter is to prevent a pending active alarm with ON condition infinitely blocking other alarm summary entries from being committed when [Alarm]SummaryMode parameter is set to 0 or 1.
Note: This parameter can also be applied to a specific cluster or alarm server process. For more information, see Configure Alarm Parameters for a Specific Cluster or Process.
Allowable Values:
0 to 20000 (minutes)
Default Value:
60