Page Table Alarm​.Stats​.Req

  • Last UpdatedMar 15, 2026
  • 4 minute read

This table provides statistics for the client requests handled by the alarm server.

Note: By default, this table is not available in the Kernel. To access this table, you need to set the INI parameter [Alarm]EnableAlarmStats to 1 prior to starting the alarm server.

Each counter presents all of the following statistics (or a subset of them).

  • Current - the number of items represented by the counter that are currently active on the alarm server.

  • Accumulated - the total number of accumulated requests since the server was started, or the statistics were reset.

  • Min - the minimum response time for handling a particular request.

  • Max - the maximum response time for handling a particular request.

  • Avg - the average response time for handling requests.

  • Total - the total accumulated response time.

Counter

Description

Available Statistics

Logon Users

The number of users logged on to the alarm server.

All

Logon Users Repeated

The number of repeated users logged on to the alarm server.

This counter is incremented when a user logs on to an alarm server where the same user has already logged on from a different process or node.

All

Logon Users Unique

The number of unique users found on the alarm server.

This counter is incremented when a user logs on to an alarm server where the same user has not already logged on from a different process or node.

All

Logon Locale Areas Repeated

The number of repeated locales and areas among the unique logon users.

Each user can be configured to have access to different areas. They can also use different languages (locales) when logging on.

This counter is incremented when a user logs on to an alarm server where the same locale and area access is already being used by other users.

Current, Accumulated

Logon Locale Areas Unique

The number of unique locales and areas among the logged on users.

This counter is incremented when a user logs on and their locale and area access is not being used by other users.

Current, Accumulated

Alarm Filters

The number of alarm filters created on the alarm server.

All

Alarm Filters Repeated

The number of repeated alarm filters encountered among the data requests received by this alarm server.

This counter is incremented when the alarm server receives an alarm data request (either an alarm list or alarm count) where the filter criteria has already been used by another request.

All

Alarm Filters Unique

The number of unique alarm filters encountered among the data requests received on the alarm server.

This counter is incremented when the alarm server receives an alarm data request (either alarm list or alarm count) where the filter criteria is different to all other requests.

All

Alarm Counts

The number of alarm count requests received by the alarm server.

All

Alarm Counts Repeated

The number of repeated alarm count requests received by this alarm server.

This counter is incremented when the alarm server receives an alarm count request that has already been received from other clients.

All

Alarm Counts Unique

The number of unique alarm count requests received by the alarm server.

This counter is incremented when the alarm server receives an alarm count request that is different to all the other requests received.

All

Alarm Count Refreshes

The number of alarm count refresh commands received by the alarm server.

Accumulated, Min, Max, Avg, Total

Alarm Count Updates

The number of alarm count value updates sent by the alarm server.

Accumulated, Min, Max, Avg, Total

Alarm Count Filter Changes

The number of alarm count change filter commands received by the alarm server.

Accumulated, Min, Max, Avg, Total

Equipment Alarm Counts

The number of alarm count requests (for equipment) received by the alarm server.

All

Equipment Alarm Counts Repeated

The number of repeated alarm count requests (for equipment) received by the alarm server.

This counter is incremented when the alarm server receives an equipment alarm count request that has already been received from other clients.

All

Equipment Alarm Counts Unique

The number of unique alarm count requests (for equipment) received by the alarm server.

This counter is incremented when the alarm server receives an equipment alarm count request that is different to all the other requests received.

All

Alarm Lists

The number of alarm list/browse requests received by the alarm server.

All

Alarm Lists Repeated

The number of repeated alarm list/browse requests received by the alarm server.

This counter is incremented when the alarm server receives an alarm list/count request that has already been received from other clients.

All

Alarm Lists Unique

The number of unique alarm list/browse requests received by the alarm server.

This counter is incremented when the alarm server receives an alarm list/browse request that is different to all the other requests received.

All

Alarm List Refreshes

The number of alarm list/browse refresh commands received on the alarm server.

Accumulated, Min, Max, Avg, Total

Alarm List Updates

The number of alarm list/browse value updates sent by the alarm server.

Accumulated, Min, Max, Avg, Total

Alarm List Filter Changes

The number of alarm list/browse change filter commands received by the alarm server.

Accumulated, Min, Max, Avg, Total

Historical Lists

The number of historical list requests (SOE or Alarm Summary) received by the alarm server.

All

Historical List Refreshes

The number of historical list change commands received by the alarm server.

Accumulated, Min, Max, Avg, Total