Situational Awareness Library

Configure a basic SA_Alarm_RuntimePage symbol

  • Last UpdatedJul 30, 2024
  • 1 minute read

The basic configuration of the SA_Alarm_RuntimePage shows current alarms from one or more ArchestrA areas. Only one custom property needs to be assigned an area name as its reference value.

Prerequisites

This procedure explains how to configure a basic symbol using a reference to an ArchestrA Area instance.

  • You must know the name of an area instance that is collecting current alarm records.

To configure the SA_Alarm_RuntimePage symbol

  1. Embed the SA_Alarm_RuntimePage symbol in another symbol from the Industrial Graphic Editor.

  2. Select the symbol.

  3. Right-click on the symbol and select Custom Properties from the shortcut menu.

  4. Select the DefaultAreaName custom property and delete its default value shown in the Default Value field.

  5. Click the icon to the left of the Default Value field to Static Text mode.

    The icon shows the letter T within a square in Static Text mode.

  6. Type the name of an area with alarm counts you want to show in the symbol and click OK.

  7. Save the symbol and check it in.

  8. Deploy the Galaxy containing the object with attributes that are used as reference values of the custom properties.

  9. Double-click an instance of InTouch ViewApp to start WindowMaker.

  10. Embed the symbol containing the symbol into an InTouch window.

  11. Run the application in WindowViewer to verify that your basic symbol configuration works correctly.