NormalizedShape Wizard option
- Last UpdatedAug 05, 2024
- 2 minute read
The Boolean value of NormalizedShape determines if the setpoint values of each spoke of a Polar Star symbol are normalized or not. The default value is True.
When set to True, all spoke setpoint values of a Polar Star symbol are normalized to produce a regularly shaped SetPoint polygon around the origin of the Polar Star spokes.
Related Wizard options and custom properties
Based on the Boolean value assigned to NormalizedShape, different sets of Wizard options and custom properties must be configured for a normalized and unnormalized Polar Star symbol.
|
Wizard options |
Custom properties |
|
NormalizedShape: True |
SpokeXPVOperatingPercent custom property: Set to an absolute percentage range around the setpoint value that represents the normalized upper and lower limits of a full scale range of measured values. |
When set to False, the setpoint values for each spoke of a Polar Star symbol are not normalized and alarm limit indicators can be shown on each spoke. Additional Wizard options and custom properties appear to select the alarm limit indicators to be shown on Polar Star spokes.
|
Wizard options |
Custom properties |
|
|---|---|---|
|
NormalizedShape: False |
SpokeXPVRangeFullScaleMax custom property: Set to the maximum of the full scale range of measured values to be shown on spokeX. |
|
|
SpokeXAlarmLimitIndicators: True |
SpokeXPVRangeFullScaleMin custom property: Set to the minimum of the full scale range of measured values to be shown on spokeX. |
|
|
SpokeXAlarmHiHiLimitIndicator:True |
SpokexAlarmHiHiLimit custom property: Set the threshold value at which the spoke X measured value transitions into a HiHi limit alarm. |
|
|
SpokeXAlarmHiLimitIndicator: True |
SpokexAlarmHiLimit custom property: Set the threshold valueat which the spoke X measured value transitions into a Hi limit alarm. |
|
|
SpokeXAlarmLoLimitIndicator: True |
SpokexAlarmLoLimit custom property: Set the threshold limit at which the spoke X measured value transitions into a Lo limit alarm. |
|
|
SpokeXAlarmLoLoLimitIndicator: True |
SpokexAlarmLoLoLimit custom property: Set the threshold limit at which the spoke X measured value transitions into a LoLo limit alarm. |
|