Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Situational Awareness Library

SpokeXPVRangeFullScaleMin custom property

  • Last UpdatedAug 06, 2024
  • 1 minute read

Sets the minimum percentage of a spoke measurement range. The symbols include the SpokexPVFullScaleMax and SpokexPVFullScaleMin custom properties to set the upper and lower limits of a measured value range with alarm limit indicators. The symbol automatically transitions into full range mode when the current measured value is outside of the range.

Assign values to the SpokexPVRangeFullScaleMin custom property

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Value

ArchestrA Automation Objects

Double

Input

Me.PVx.EngUnitsRangeMin

Reference to an ArchestrA object's EngUnitsRangeMax attribute or a static number.

Spoke1PVRangeFullScaleMin=PUMP_001.Volume.EngUnitsRangeMin

Spoke1PVRangeFullScaleMin=200.0

InTouch Tags

Real

Input

Galaxy:Me.PVx.EngUnitsRangeMin

Reference to an InTouch tag

Spoke1PVRangeFullScaleMin=TankVolume.MinEU

The NormalizedShape Wizard option must be set to False to show the SpokexPVRangeFullScaleMin custom property.