Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Situational Awareness Library

oPVRangeOperatingAutoScale custom property

  • Last UpdatedAug 06, 2024
  • 2 minute read

The SA_OperatingRange symbol includes the oPVRangeOperatingAutoScale custom property.

When oPVRangeOperatingAutoScale is True, the SA_OperatingRange symbol uses the value of the oPVRangeOperatingPercent custom property to set percentage boundaries above and below a setpoint value to establish a normal operating range. When a measured value is outside of the normal operating range around the setpoint, the symbol goes into full range mode and displays full range flags.

The reference value of oPVOperatingPercent is used to internally calculate updated oPVRangeOperatingMin and oPVRangeOperatingMax custom property values using the following formulas:

  • oPVRangeOperatingMin = Setpoint - (oPVOperatingPercent/100 x Setpoint)

  • oPVRangeOperatingMax = Setpoint + (oPVOperatingPercent/100 x Setpoint)

    Note: Make sure the object attribute references to both custom properties are writeable during run time.

During run time, the symbol uses the percentage range around the setpoint as the symbol's graphic scale with the setpoint always at the midpoint between the minimum and maximum limits. When a measured value moves outside of the percentage range around the setpoint, the symbol's graphic scale changes to use the limits set by the oPVRangeFullScaleMin and oPVRangeFullScaleMax custom properties. The symbol shows full scale flags to indicate that it is in full range mode.

If oPVRangeOperatingAutoScale is set to False during run time, new values need to be set for the oPVRangeOperatingMin and oPVRangeOperatingMax custom properties. Otherwise, they remain according to the last calculation.

Assign values to the oPVRangeOperatingAutoScale custom property

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Values

ArchestrA Automation Objects

Boolean

Input

False

Reference to an attribute or a static Boolean value

oPVRangeOperatingAutoScale=True

InTouch Tags

Discrete

Input

False

Reference to an InTouch tag or a static Boolean value

oPVRangeOperatingAutoScale=True

Associated Wizard options

  • Orientation: True

  • OperatingAutoScaleEnabled

Associated custom properties

  • oPVRangeOperatingAutoScale

  • oPVRangeOperatingMax

  • oPVRangeOperatingMin

In This Topic