SpokeXAlarmMostUrgentShelved custom property
- Last UpdatedAug 06, 2024
- 1 minute read
The Boolean value of SpokexAlarmMostUrgentShelved indicates if the most urgent alarm associated with a Polar Star spoke's measured value is currently shelved or not. The default is False to indicate an alarm has not been shelved.
Assign values to the AlarmMostUrgentShelved custom property
Alarm Border animation is primarily intended for managed applications that use ArchestrA objects, which include a set of aggregate alarming attributes. These attributes can be assigned as references to a symbol's set of Alarm Border animation custom properties.
Applications that only use tag-based references do not have a comparable set of aggregate alarming attributes. References to your aggregate alarm data must assigned to the custom properties of Situational Awareness Library symbols that are part of tag-based applications.
|
Application Type |
Data Type |
Custom Property Type |
Default Value |
Example Custom Property Value |
|
ArchestrA Automation Objects |
Boolean |
Input |
False |
Reference to an ArchestrA object's AlarmMostUrgentShelved attribute. Spoke1AlarmMostUrgentShelved=TIT001.PV.AlarmMostUrgentShelved |
|
InTouch Tags |
Discrete |
Input |
False |
InTouch tag that references aggregate alarm acknowledgement status. |
Related Wizard options and custom properties
The SpokexAlarmBorder Wizard option must be set to True to show the SpokexAlarmMostUrgentShelved custom property.
The following custom properties are set with SpokexAlarmMostUrgentShelved to enable Alarm Border animation around a symbol
-
SpokexAlarmIndicatorVisible
-
SpokexAlarmMostUrgentInAlarm
-
SpokexAlarmMostUrgentMode
-
SpokexAlarmMostUrgentSeverity
-
AlarmMostUrgentAcked