PVRangeFullScaleMax custom property - AmpsMeter

  • Last UpdatedAug 06, 2024
  • 1 minute read

Sets the maximum limit of a measured value that can be shown on the meter of the SA_AmpsMeter symbol. The PVRangeFullScaleMax and PVRangeFullScaleMin custom properties set the upper and lower limits of a measured value range shown on the symbol's meter bar.

Assign values to the PVRangeFullScaleMax custom property

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Value

ArchestrA Automation Objects

Double

Input

20.0

Reference to an ArchestrA object's EngUnitsRangeMax attribute or a static value.

PVRangeFullScaleMax=PUMP_001.PV.EngUnitsRangeMax

PVRangeFullScaleMax=200.0

InTouch Tags

Real

Input

20.0

Reference to an InTouch tag

PVRangeFullScaleMax=TankVolume.MaxEU

No Wizard options need to be configured to show the PVRangeFullScaleMax custom property.

The PVRangeFullScaleMin custom property must be configured with PVRangeFullScaleMax to define a range of possible measured values that can be shown on a meter bar.