SpokeXAlarmMostUrgentInAlarm custom property
- Last UpdatedAug 06, 2024
- 1 minute read
The Boolean value ofSpokexlarmMostUrgentInAlarm indicates if the most urgent alarm is active for spoke X of a Polar Star symbol.
During an active alarm state, the appearance of the Alarm Border changes when the most urgent alarm is active. An Alarm Border remains around a Polar Star spoke until the measured value returns to normal and the alarm is acknowledged.
Assign values to the SpokeXAlarmMostUrgentInAlarm custom property
Alarm Border animation is primarily intended for managed applications that use ArchestrA objects, which include a set of aggregate alarming attributes. These attributes can be assigned as references to a symbol's set of Alarm Border animation custom properties.
Applications that only use tag-based references do not have a comparable set of aggregate alarming attributes. References to your aggregate alarm data must assigned to the custom properties of Situational Awareness Library symbols that are part of tag-based applications.
|
Application Type |
Data Type |
Custom Property Type |
Default Value |
Example Custom Property Value |
|
ArchestrA Automation Objects |
Boolean |
Input |
Me.PV.AlarmMostUrgentInAlarm |
Reference to an ArchestrA object's AlarmMostUrgentAcked attribute. Spoke1AlarmMostUrgentInAlarm=TIT001.PV.AlarmMostUrgentInAlarm |
|
InTouch Tags |
Discrete |
Input |
Galaxy:Me.PV.AlarmMostUrgentInAlarm |
InTouch tag that references the status of the most urgent aggregate alarm. |
Related Wizard options and custom properties
The SpokexAlarmBorder Wizard option must be set to True to show the SpokexAlarmMostUrgentInAlarm custom property.
The following custom properties are set with SpokexAlarmMostUrgentInAlarm to enable Alarm Border animation around a Polar Star spoke.
-
SpokexAlarmIndicatorVisible
-
AlarmMostUrgentAcked
-
SpokexAlarmMostUrgentInMode
-
SpokexAlarmMostUrgentSeverity
-
SpokexAlarmMostUrgentShelved