Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Situational Awareness Library

CommandPanel Wizard option

  • Last UpdatedAug 05, 2024
  • 1 minute read

The Boolean value of CommandPanel shows or hides a command panel on a SA_AlarmSeverity symbol configured as an alarm panel. The default is True to show the panel.

A command panel provides a list of alarm mode options. During run time, operators can change the mode of active alarms in an area to Enable, Disable, Silence, or Inhibit. Without a command panel, an alarm panel shows the current alarm mode.

The Type Wizard option must be set to AlarmPanel to show the CommandPanel Wizard option. Two additional custom properties must be configured when CommandPanel is set to True.

Wizard options

Custom properties

Type=AlarmPanel

CommandPanelControlVisible custom property: Set to True to show a command panel on an alarm panel.

CommandPanel=True

AlarmModeCmd custom property: Assign the AlarmModeCmd attribute of an ArchestrA area object as the reference value of custom property.

Related Links