AlarmMostUrgentSeverity custom property
- Last UpdatedAug 06, 2024
- 1 minute read
The integer value (1-4) of AlarmMostUrgentSeverity indicates the current severity of a symbol's most urgent alarm. Alarm severity is displayed as an integer in the alarm indicator icon shown with Alarm Border animation.
Assign values to the AlarmMostUrgentSeverity custom property
Alarm Border animation is primarily intended for managed applications that use ArchestrA automation objects, which include a set of aggregate alarming attributes. These attributes can be assigned as references to a symbol's set of Alarm Border animation custom properties.
Modern applications that use tag-based references do not have a comparable set of aggregate alarming attributes. References to your aggregate alarm data must assigned to the custom properties of Situational Awareness Library symbols that are part of tag-based Modern applications.
|
Application Type |
Data Type |
Custom Property Type |
Default Value |
Example Custom Property Value |
|
ArchestrA Automation Objects |
Integer |
Input |
Me.PV.AlarmMostUrgentSeverity |
Reference to an ArchestrA object's AlarmMostUrgentSeverity attribute. AlarmMostUrgentSeverity=UDA01.Volume.AlarmMostUrgentSeverity |
|
InTouch Tags |
Integer |
Input |
Galaxy:Me.PV.AlarmMostUrgentSeverity |
InTouch tag that references the severity of the most urgent aggregate alarm. |
Related Wizard options and custom properties
The following Wizard options must be set to their listed values to expose the AlarmMostUrgentSeverity custom property.
-
SymbolMode: Advanced
Note: Some symbols do not include the SymbolMode Wizard option. The AlarmBorder Wizard option is included in the basic set of Wizard options.
-
AlarmBorder: True
The following custom properties are set with AlarmMostUrgentSeverity to enable Alarm Border animation around a symbol
-
AlarmIndicatorVisible
-
AlarmMostUrgentAcked
-
AlarmMostUrgentInAlarm
-
AlarmMostUrgentMode
-
AlarmMostUrgentShelved