Pen_AlarmMostUrgentSeverity custom property
- Last UpdatedAug 06, 2024
- 1 minute read
The integer value (1-4) of Pen_AlarmMostUrgentSeverity indicates the current severity of the SA_Trend_SinglePen symbol's most urgent alarm. Alarm severity is displayed as an integer in the alarm indicator icon shown with Alarm Border animation.
Assign values to the Pen_AlarmMostUrgentSeverity custom property
Alarm Border animation is primarily intended for applications that use ArchestrA objects, which include a set of aggregate alarming attributes. These attributes can be assigned as references to a symbol's set of Alarm Border animation custom properties.
Modern applications that use tag-based references do not have a comparable set of aggregate alarming attributes. References to your aggregate alarm data must assigned to the custom properties of Situational Awareness Library symbols that are part of tag-based Modern applications.
|
Application Type |
Data Type |
Custom Property Type |
Default Value |
Example Custom Property Value |
|
ArchestrA Automation Objects |
Integer |
Input |
Me.PV.AlarmMostUrgentSeverity |
Reference to an ArchestrA object's AlarmMostUrgentSeverity attribute. Pen_AlarmMostUrgentSeverity=PUMP.PV.AlarmMostUrgentSeverity |
|
InTouch |
Integer |
Input |
Galaxy:Me.PV.AlarmMostUrgentSeverity |
InTouch tag that references the severity of the most urgent aggregate alarm. Pen_AlarmMostUrgentSeverity=AlarmSeverity |
Related Wizard options and custom properties
The following Wizard options must be set to their listed values to show the Pen_AlarmMostUrgentSeverity custom property.
-
SymbolMode: Advanced
-
AlarmBorder: True
The following custom properties are set with Pen_AlarmMostUrgentSeverity to enable Alarm Border animation around a symbol
-
Pen_AlarmIndicatorVisible
-
Pen_AlarmMostUrgentAcked
-
Pen_AlarmMostUrgentInAlarm
-
Pen_AlarmMostUrgentMode
-
Pen_AlarmMostUrgentShelved