Configure a basic SA_Valve_2WayAngle symbol using ArchestrA attributes
- Last UpdatedJul 30, 2024
- 3 minute read
The basic configuration of a SA_Valve_2WayAngle symbol is discrete valve. A single custom property needs to be configured to show the active and passive states of the symbol. The basic configuration of an analog SA_Valve_2WayAngle symbol requires you to set three additional custom properties to show the valve open percentage on the symbol's valve position bar.
|
Discrete Passive |
Discrete Active |
Analog Passive |
Analog Active |
|
|
|
|
|
The steps to configure a basic discrete or analog 2WayAngle valve symbol are explained in the following procedure. A caption within the procedure identifies the additional steps to assign reference values to the custom properties of an analog valve.
Discrete valve prerequisites
To follow the steps to configure a basic discrete valve, create ArchestrA objects that meet the following requirements:
-
Create a Boolean field attribute to indicate the state of the valve.
-
Create an InTouch application with a window to verify that the symbol has been configured correctly.
Analog valve prerequisites
To follow the steps to configure a basic analog valve, create ArchestrA objects that meet the following requirements:
-
Create a Boolean field attribute to indicate the state of the valve..
-
Create a Double data type field attribute for the valve's PV value shown as the open percentage on the valve position bar.
Note: The symbol includes two other custom properties to set the upper and lower limits of the measured value range. Static values of 0 and 100 are used as the values for the lower and upper limits of the range.
-
Create an InTouch application with a window to verify that the symbol has been configured correctly.
To configure a basic SA_Valve_2WayAngle symbol using ArchestrA attributes
-
Embed the symbol in another symbol in the Industrial Graphic Editor.
-
Select the symbol.
-
Right-click on the symbol and select Custom Properties from the shortcut menu to show the Custom Properties dialog box.
-
Select the EquipStateActive custom property from the list and click the Galaxy Browser button to the right of the Default Value field.
-
Click the Attribute Browser tab and select an attribute from the list to assign to the custom property.
-
Assign a Boolean reference value to the EquipStateActive custom property and click OK.
-
Continue at Step 13 of this procedure
Specific steps to configure a basic analog 2WayAngle valve symbol
-
Set the ValveType Wizard option to Analog.
-
Select the PV custom property from the list and click the Galaxy Browser button to the right of the Default Value field.
-
Assign a Double attribute as the reference value for the PV custom property and click OK.
-
Assign 100 as the value of the PVMax custom property.
-
Assign 0 as the value of the PVMin custom property and click OK.
-
Save the symbol and check it in.
-
If necessary, deploy the Galaxy containing the object with attributes that are used as reference values of the custom properties.
-
Double-click an instance of InTouch ViewApp to start WindowMaker.
-
Create a new InTouch window and embed the symbol containing the 2WayAngle valve symbol.
-
Run the application in WindowViewer to verify that your basic symbol configuration works correctly.