EquipXModeNormal custom property
- Last UpdatedAug 06, 2024
- 1 minute read
The string value of EquipXModeNormal specifies one or more normal equipment control modes of equipment with values A, M, or C. Place a comma between characters when equipment has multiple normal controlmodes.
An equipment Control Mode Indicator does not show any character to indicate a piece of equipment is running in Normal controlmode.
Assign values to the EquipXModeNormal custom property
|
Application Type |
Data Type |
Custom Property Type |
Default Value |
Example Custom Property Values |
|
ArchestrA Automation Objects |
String |
Input |
Null |
Reference to an ArchestrA attribute or a static string. Equip1ModeNormal=ODA1.ControllerModeN Equip1ModeNormal="A,C" |
|
InTouch Tags |
Message |
Input |
Null |
Reference to an InTouch tag or a static string. Equip1ModeNormal=Equip1ModeN Equip1ModeNormal="A,C" |
Related Wizard options and custom properties
The following Wizard options must be set to their listed values to expose the ControllerOPModeNormal custom property.
-
SymbolMode: Advanced
-
ControlModeIndicator: True
The following custom properties must be set with EquipXModeNormal to set all possible control modes of a piece of equipment.
-
EquipXModeAuto
-
EquipXModeCascade
-
EquipXModeManual