Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Situational Awareness Library

Medium Alarm Severity 3 symbol component

  • Last UpdatedAug 01, 2024
  • 2 minute read

AlarmSeverity3MediumIcon

An alarm severity 3 medium indicator shows the count of active or shelved severity 3 alarms from an ArchestrA area object or other types of ArchestrA objects. The indicator includes a blue triangle icon when the severity 3 count is 1 or greater.

When the alarm severity 3 medium count is 0, the alarm severity 3 high indicator can be configured to be hidden on an alarm severity indicator by setting the AlarmCntsBySeverity3Visible or AlarmCntsBySeverity3ShlvdVisible custom properties to their corresponding object attributes. An alarm severity 3 medium indicator can be configured to show 0 as the count and a gray triangle by setting the AlarmCntsBySeverity3Visible or AlarmCntsBySeverity3ShlvdVisible custom properties to True.

To configure an alarm severity 3 medium symbol component

An alarm severity indicator can show active or shelved alarm counts by severity based on the Boolean value of the ShelvedEnable Wizard option. When set to True, the alarm severity indicator shows shelved alarm counts.

Wizard options

Custom properties

Type Wizard option - Alarm AlarmSeverityIndicator

AlarmCntsbySeverity3EnableShlvd custom property: Set to the AlarmCntsBySeverityEnableShelved[3] attribute of an object for shelved alarm severity 3 counts.

ShelvedEnable Wizard option: True | False

AlarmCntsBySeverity3ShlvdVisible custom property: Set to AlarmCntsBySeverityEnableShelved[3] > 0 attribute of an area object to show shelved alarm severity 3 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and triangle icon.

AlarmSeverity3Indicator Wizard option True

Active Alarm Counts custom properties

AlarmCntsBySeverity3 custom property Set to the AlarmCntsBySeverity[3] attribute of an object for active alarm severity 3 counts.

AlarmCntsBySeverity3Visible custom property: Set to AlarmCntsBySeverity[3] > 0 attribute of an area object to show active alarm severity 3 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and triangle icon.