PVOperatingPercent custom property

  • Last UpdatedAug 06, 2024
  • 2 minute read

The value of PVOperatingPercent sets percentage boundaries above and below a setpoint value to establish a normal operating range. When a measured value is outside of the normal operating range around the setpoint, the symbol goes into full range mode and displays full range flags. Operators can glance at a set of symbols and quickly identify which measured value is in an abnormal state

In order to set a percent operating range around a setpoint during run time, the PVRangeOperatingAutoScale custom property must be set to True. When PVRangeOperatingAutoScale is True, the symbol internally calculates updated PVRangeOperatingMin and PVRangeOperatingMax custom property values using the following formulas:

  • PVRangeOperatingMin = Setpoint - (PVOperatingPercent/100 x Setpoint)

  • PVRangeOperatingMax = Setpoint + (PVOperatingPercent/100 x Setpoint)

    Note: Make sure the object attribute references to both custom properties are writable during run time.

During run time, the symbol uses the percentage range around the setpoint as the symbol's graphic scale with the setpoint always at the midpoint between the minimum and maximum limits. When a measured value moves outside of the percentage range around the setpoint, the symbol's graphic scale changes to use the limits set by the PVRangeFullScaleMin and PVRangeFullScaleMax custom properties. The symbol shows Full scale flags at the ends of its graphic scale to indicate that it is in full range mode.

If PVRangeOperatingAutoScale is set to False during run time, new values need to be set for the PVRangeOperatingMin and PVRangeOperatingMax custom properties. Otherwise, they remain according to the last calculation.

Assign values to the PVOperatingPercent custom property

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Values

ArchestrA Automation Objects

Integer

Input

0

Reference to an attribute or a static value.

PVOperatingPercent=40

InTouch Tags

Integer

Input

0

Reference to an InTouch tag or a static value.

PVOperatingPercent=OptRangePercent

PVOperatingPercent=30

Associated Wizard options

Associated custom properties

  • PVRangeOperatingAutoScale: True

  • PVRangeOperatingMax

  • PVRangeOperatingMin