Pen_RangeOptimalMin custom property
- Last UpdatedAug 06, 2024
- 1 minute read
The value of Pen_RangeOptimalMin sets the minimum limit of an optimal range of measured values shown on the trend grid of the SA_Trend_SinglePen symbol.
A gray shaded area appears the full width of the trend grid to indicate the optimal range of measured values set by the Pen_RangeOptimalMin and PenRangeOptimalMax custom properties.
Assign values to the Pen_RangeOptimalMin custom property
|
Application Type |
Data Type |
Custom Property Type |
Default Value |
Example Custom Property Values |
|
ArchestrA Automation Objects |
Double |
Input |
0.0 |
Reference to an ArchestrA object attribute or a static numeric value Pen_RangeOptimalMin=1600 |
|
InTouch Tags |
Real |
Input |
0.0 |
Reference to an InTouch tag or a static numeric value Pen_RangeOptimalMin=OptRangeMax Pen_RangeOptimalMin=1600 |
Related Wizard options and custom properties
The following Wizard options must be set to their listed values to expose the Pen_RangeOptimalMin custom property.
-
SymbolMode: Advanced
-
OptimalRange: True
The following custom properties must be set with Pen_RangeOptimalMin to show an optimal range.
-
Pen_RangeOptimalVisible
-
Pen_RangeOptimalMax