Situational Awareness Library

High Alarm Severity 2 symbol component

  • Last UpdatedJul 29, 2024
  • 2 minute read

AlarmSeverity2HighIcon

An alarm severity 2 high indicator shows the count of active or shelved severity 2 alarms from an ArchestrA area object or other types of ArchestrA objects. The indicator includes a yellow square icon when the severity 2 count is 1 or greater.

When the alarm severity 2 high count is 0, the alarm severity 2 high indicator can be configured to be hidden on an alarm severity indicator by setting the AlarmCntsBySeverity2Visible or AlarmCntsBySeverity2ShlvdVisible custom properties to their corresponding object attributes. An alarm severity 2 high indicator can be configured to show 0 as the count and a gray square by setting the AlarmCntsBySeverity2Visible or AlarmCntsBySeverity2ShlvdVisible custom properties to True.

To configure an alarm severity 2 high symbol component

An alarm severity indicator can show active or shelved alarm counts by severity based on the Boolean value of the ShelvedEnable Wizard option. When set to True, the alarm severity indicator shows shelved alarm counts.

Wizard options

Custom properties

Type Wizard option - Alarm AlarmSeverityIndicator

AlarmCntsBySeverity2EnableShlvd custom property: Set to the AlarmCntsBySeverityEnableShelved[2] attribute of an object for shelved alarm severity 2 counts.

ShelvedEnable Wizard option: True | False

AlarmCntsBySeverity2ShlvdVisible custom property: Set to AlarmCntsBySeverityEnableShelved[2] > 0 attribute of an area object to show shelved alarm severity 2 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and square icon.

AlarmSeverity2Indicator Wizard option: True

Active Alarm Counts custom properties

AlarmCntsBySeverity2 custom property: Set to the AlarmCntsBySeverity[2] attribute of an area object for active alarm severity 2 counts.

AlarmCntsBySeverity2Visible custom property: Set to AlarmCntsBySeverity[2] > 0 attribute of anobject to show active alarm severity 2 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and square icon.