Critical Alarm Severity 1 symbol component
- Last UpdatedJul 29, 2024
- 2 minute read

A Critical alarm (Severity 1) indicator shows the count of active or shelved severity 1 alarms from an ArchestrA area object or other types of ArchestrA objects. The indicator includes a red diamond icon when the severity 1 count is 1 or greater.
When the alarm severity 1 critical count is 0, the alarm severity 1 critical indicator can be configured to be hidden on an alarm severity indicator by setting the AlarmCntsBySeverity1Visible or AlarmCntsBySeverity1ShlvdVisible custom properties to their corresponding object attributes. An alarm severity 1 critical indicator can be configured to show 0 as the count and a gray diamond by setting the AlarmCntsBySeverity1Visible or AlarmCntsBySeverity1ShlvdVisible custom properties to True.
To configure an alarm severity 1 critical symbol component
An alarm severity indicator can show active or shelved alarm counts by severity based on the Boolean value of the ShelvedEnable Wizard option. When set to True, the alarm severity indicator shows shelved alarm counts.
|
Wizard options |
Custom properties |
|
Type Wizard option - Alarm: AlarmSeverityIndicator |
AlarmCntsBySeverity1EnableShlvd custom property: Set to the AlarmCntsBySeverityEnableShelved[1] attribute of an object for shelved alarm severity 1 counts. |
|
ShelvedEnable Wizard option: True | False |
AlarmCntsBySeverity1ShlvdVisible custom property: Set to AlarmCntsBySeverityEnableShelved[1] > 0 attribute of an area object to show shelved alarm severity 1 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and diamond icon. |
|
Active Alarm Counts custom properties |
|
|
AlarmCntsBySeverity1 custom property: Set to the AlarmCntsBySeverity[1] attribute of an area object for active alarm severity 1 counts. |
|
|
AlarmCntsBySeverity1Visible custom property: Set to AlarmCntsBySeverity[1] > 0 attribute of an object to show active alarm severity 1 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and diamond icon. |
|