Low Alarm Severity 4 symbol component

  • Last UpdatedAug 01, 2024
  • 2 minute read

AlarmSeverity4LowIcon

An alarm severity 4 Low indicator shows the count of active or shelved severity 4 alarms from an ArchestrA area object or other types of ArchestrA objects. The indicator includes a magenta triangle icon when the severity 4 count is 1 or greater.

When the alarm severity 4 medium count is 0, the alarm severity 4 low indicator can be configured to be hidden on an alarm severity indicator by setting the AlarmCntsBySeverity4Visible or AlarmCntsBySeverity4ShlvdVisible custom properties to their corresponding object attributes. An alarm severity 4 low indicator can be configured to show 0 as the count and a gray triangle by setting the AlarmCntsBySeverity4Visible or AlarmCntsBySeverity4ShlvdVisible custom properties to True.

To configure an alarm severity 4 critical symbol component

An alarm severity indicator can show active or shelved alarm counts by severity based on the Boolean value of the ShelvedEnable Wizard option. When set to True, the alarm severity indicator shows shelved alarm counts.

Wizard options

Custom properties

Type Wizard option - Alarm AlarmSeverityIndicator

AlarmCntsBySeverity4EnableShlvd custom property: Set to the AlarmCntsBySeverityEnableShelved[4] attribute of an object for shelved alarm severity 4 counts.

ShelvedEnable Wizard option: True | False

AlarmCntsBySeverity4ShlvdVisible custom property: Set to AlarmCntsBySeverityEnableShelved[4] > 0 attribute of an area object to show shelved alarm severity 4 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and triangle icon.

AlarmSeverity4Indicator Wizard option: True

Active Alarm Counts custom properties

AlarmCntsBySeverity4 custom property: Set to the AlarmCntsBySeverity[4] attribute of an object for active alarm severity 1 counts.

AlarmCntsBySeverity4Visible custom property: Set to AlarmCntsBySeverity[4] > 0 attribute of an area object to show active alarm severity 4 indicator on an alarm severity indicator. Set to a static Boolean True to show a 0 gray count and triangle icon.