Situational Awareness Library

oROCPercentMax custom property

  • Last UpdatedAug 06, 2024
  • 1 minute read

The value of oROCPercentMax sets an absolute percent rate of change between consecutive measured values. The trend of recent measured values is represented by the upward or downward orientation of a ROC arrow symbol shown next to a symbol.When consecutive measured values exceed the ROCPercentMax percentage, the ROC arrow points upward or downward to indicate the trend of recent measured values.

Also, when a measured value's rate of change exceeds the value of ROCPercentMax, a rate of change alarm occurs if ROC properties have been set for an object attribute.

Assign values to the oROCPercentMax custom property

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Values

ArchestrA Automation Objects

Integer

Input

0

Reference to an attribute or a static value

oROCPercentMax=UDA01.Volume.ROC.Rate1

oROCPercentMax=10

InTouch Tags

Integer

Input

0

Reference to an InTouch tag or a static value

ROCPercentMax=ROCRatePercent

ROCPercentMax=10

1 ROC alarm properties must be set for an object to expose the ROC.Rate attribute.