Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

Situational Awareness Library

AlarmMostUrgentMode custom property

  • Last UpdatedAug 06, 2024
  • 1 minute read

The integer value of AlarmMostUrgentMode indicates the current mode of the most urgent alarm associated with a symbol's measured value. Alarm modes are no alarms, enabled, silenced, disabled, or shelved.

Alarm Mode

Integer

No alarms

0

Alarms enabled

1

Alarms disabled

2

Alarms silenced

3

Alarms shelved

4

Assign values to the AlarmMostUrgentMode custom property

Alarm Border animation is primarily intended for managed applications that use ArchestrA automation objects, which include a set of aggregate alarming attributes. These attributes can be assigned as references to a symbol's set of Alarm Border animation custom properties.

Modern applications that use tag-based references do not have a comparable set of aggregate alarming attributes. References to your aggregate alarm data must assigned to the custom properties of Situational Awareness Library symbols that are part of tag-based Modern applications.

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Value

ArchestrA Automation Objects

Integer

Input

Me.PV.AlarmMostUrgentMode

Reference to an ArchestrA object's AlarmMostUrgentMode attribute.

AlarmMostUrgentMode=UDA01.Volume.AlarmMostUrgentMode

InTouch Tags

Integer

Input

Galaxy:Me.PV.AlarmMostUrgentMode

InTouch tag that references the mode of the most urgent aggregate alarm.

The following Wizard options must be set to their listed values to expose the AlarmMostUrgentInAlarm custom property.

  • SymbolMode: Advanced

    Note: Some symbols do not include the SymbolMode Wizard option. The AlarmBorder Wizard option is included in the basic set of Wizard options.

  • AlarmBorder: True

The following custom properties are set with AlarmMostUrgentAcked to enable Alarm Border animation around a symbol

  • AlarmIndicatorVisible

  • AlarmMostUrgentAcked

  • AlarmMostUrgentInAlarm

  • AlarmMostUrgentSeverity

  • AlarmMostUrgentShelved

In This Topic