Configure a basic SA_Valve_And_Damper symbol using InTouch tags
- Last UpdatedJul 30, 2024
- 2 minute read
The basic configuration of a SA_Valve_And_Damper symbol is a discrete valve oriented horizontally with a MOV actuator. A Wizard option and two custom properties need to be configured to detect the symbol's open and closed valve actuator states.
|
Closed Valve |
Open Valve |
|
|
|
Prerequisites
This procedure explains how to configure a basic symbol using a reference to an InTouch tag.
-
Create two Discrete tags to indicate the positions of the symbol's limit switches.
-
Create an InTouch application with a window to verify that the symbol has been configured correctly.
To configure a basic SA_Valve_And_Damper symbol
-
Drop the symbol in a WindowMaker window.
-
Double-click on the symbol to show the Edit Symbol Properties dialog box.
-
Click the Wizard options tab and select LimitSwitches.
-
Select the Dual option.
-
Click the Custom Properties tab to show the default custom properties.
-
Click the Browse Galaxy button to the right of the Default Value field to show the Select Tag dialog box.
-
Assign an InTouch tag as the reference value of the LimitSwitchClosed custom property.
-
Assign an InTouch tag as the reference value of the LimitSwitchOpen custom property.
-
If you want, assign optional string values as the symbol's label.
-
Right-click on the symbol, select Substitute, and then select Substitute Strings.
-
Enter a string value for Label and click OK.
-
-
Save your changes.
-
Run the application containing the symbol in WindowViewer to verify that your configuration changes are correct.