Configure a basic SA_Valve_2Way symbol using InTouch tags
- Last UpdatedJul 30, 2024
- 3 minute read
The basic configuration of a SA_Valve_2Way symbol is discrete valve. A single custom property needs to be configured to show the active and passive states of the symbol.
The basic configuration of an analog SA_Valve_2Way symbol requires you to set three additional custom properties to show the valve open percentage on the symbol's valve position bar.
|
Discrete Passive |
Discrete Active |
Analog Passive |
Analog Active |
|
|
|
|
|
The steps to configure a basic discrete or analog 2Way valve symbol are explained in the following procedure. A caption within the procedure identifies the additional steps to assign reference values to the custom properties of an analog valve.
Discrete valve prerequisites
This procedure explains how to configure a basic symbol using a reference to an InTouch tag.
-
Create a Discrete tag.
-
Create an InTouch application with a window to verify that the symbol has been configured correctly.
Analog valve prerequisites
To follow the steps to configure a basic analog valve, create InTouch tags that meet the following requirements:
-
Create a Discrete tag to indicate the state of the valve.
-
Create a Real tag for the valve's PV value shown as the open percentage on the valve position bar.
Note: The symbol includes two other custom properties to set the upper and lower limits of the measured value range. Static values of 0 and 100 are used as the values for the lower and upper limits of the range.
-
Create an InTouch application with a window to verify that the symbol has been configured correctly.
To configure a basic SA_Valve_2Way symbol using InTouch tags
-
Drop the symbol in a WindowMaker window.
-
Double-click on the symbol to show the Edit Symbol Properties dialog box.
-
Click the Custom Properties tab to show the default custom properties.
-
Click the Browse Galaxy button to the right of the Default Value field to show the Select Tag dialog box.
-
Assign a Discrete InTouch tag as the reference value of the EquipStateActive custom property.
-
Continue at step 12 of this procedure.
Specific steps to configure a basic analog 2Way valve symbol
-
Set the ValveType Wizard option to Analog.
-
Select the PV custom property from the list and click the Browse Galaxy button to the right of the Default Value field.
-
Assign a Real InTouch tag as the reference value for the PV custom property and click OK.
-
Assign 100 as the value of the PVMax custom property.
-
Assign 0 as the value of the PVMin custom property and click OK.
-
Save your changes.
-
Run the application containing the symbol in WindowViewer to verify that your configuration changes are correct.