Situational Awareness Library

ControlModeNormal custom property

  • Last UpdatedAug 06, 2024
  • 1 minute read

String value that specifies one or more normal operational modes. Assigned values can be A, M, or C. Place a comma between characters when there are two or more normal operational modes.

A Control Mode icon does not show any character to represent Normal operational mode.

Assign values to the ControlModeNormal custom property

Application Type

Data Type

Custom Property Type

Default Value

Example Custom Property Values

ArchestrA Automation Objects

String

Input

Null

Assign a String ArchestrA Object attribute.

ControlModeNormal=ODA.NormalMode

InTouch Tags

Message

Input

Null

Assign a String InTouch tag.

ControlModeNormal=NormalMode

The following Wizard options must be set to their listed values to show the ControlModeNormal custom property.

  • SymbolMode: Advanced

  • ControlModeIndicator: True

The following custom properties must be assigned reference values to define the possible operational modes of a piece of equipment.

  • ControlModeAuto

  • ControlModeCascade

  • ControlModeManual

  • ControlModeNormal