AS - Cable Temperature Calculation
- Last UpdatedJul 14, 2025
- 3 minute read
Step – I Cable Temperature (If total calculated de-rating Cd <=1
0 = A + ( [R - A] * [I0 / IR * Ct* Pc ]2 )
Where:
I0 = operating current, in amperes
IR = rated current of cable, in amperes
0 = operating temperature of cable when carrying I0, in degrees Celsius
R = rated or maximum operating temperature determined from Table 1 when carrying IR, in degrees Celsius
A = ambient air or soil temperature, in degrees Celsius
Ct = ambient temperature de-rating factor (De-rating factor for Ambient Temperature (Cat))
Pc = number of cables in parallel

For External Situation = ‘Air/Concrete’
Then set A = 40
Else set A = 25

IR = Max. Current:

I0 = Design Current: This is the Cable Current column.

R = Conductor Temperature:

Pc = No. of Cables:
Step – II Cable Temperature (If total calculated de-rating Cd >1)
0 = A + ( [R - A] * [I0 / IR * Cd * Pc]2 )
Where:
I0 = operating current, in amperes
IR = rated current of cable, in amperes
0 = operating temperature of cable when carrying I0, in degrees Celsius
R = rated or maximum operating temperature determined from Table 1 when carrying IR, in degrees Celsius
A = ambient air or soil temperature, in degrees Celsius
Cd = total calculated derating
Pc = number of cables in parallel
Results of this calculation are displayed in Sizing Result tab as shown below.