Please ensure Javascript is enabled for purposes of website accessibility
Powered by Zoomin Software. For more details please contactZoomin

AVEVA™ Electrical

Calculate Single Cable Size

  • Last UpdatedAug 08, 2025
  • 6 minute read

To calculate a cable size for a load:

  1. Select the cable from the Cable Schedule list, then click Cable Sizing in the Tools section of the List Tools - Cable Schedule tab.

  2. If the equipment voltage exceeds the cable size range, the following message is displayed.

    In such cases, cable cannot be sized using this method.

  3. Otherwise, the Cable Sizing window is then displayed.

    Note:
    The first time that the Cable Sizing window is accessed the following disclaimer is displayed:



    The message can be viewed again from a link on the Cable Sizing window.

  4. The layout of the window depends on the cable sizing standard selected in AVEVA Engineering. For example, if the BS standard is selected, the following is displayed.

    Note:
    For further details of the Cable Sizing window, refer to the Common Functionality User Guide.

    Note:
    The layout of the window is also different if the selected cable was imported from ETAP (using Electrical Engineer). Refer to Calculate Single ETAP Cable Size for details.

    Note:
    If user-defined cable sizing equations from a spreadsheet are to be used, check the External Cable Sizing checkbox. Refer to External Cable Sizing for details.

    Note:
    If the cable is frozen or on a locked drum, it cannot be edited. The OK and Apply buttons in the Cable Sizing window will be disabled.

  5. Whichever standard is in use, select the appropriate details on the Cable Sizing tab and complete the Cable Length field.

    Note:
    If no length is entered, cable sizing may still take place using a default length if Zero Length Cable Sizing is enabled in AVEVA Engineering.

    Note:
    For the IEC standard, the minimum value that may be saved in the Permitted Volt Drop and Starting Volt Drop fields is 0.05.
    The maximum value permitted for the Permitted Volt Drop field is 20. The maximum value permitted for the Starting Volt Drop field is 30.

  6. From the External Situation list, select either Free Air or Buried Underground. The middle section of the tab then changes to display the fields relevant to the selected situation. For example:

    or:

  7. The Fault Protection tab includes two further tabs, Short Circuit and Earth Current:

  8. On the Short Circuit tab, complete the details as required, and click the Calculate Short Circuit button to calculate the minimum required core size.

  9. On the Earth Current tab, enter the voltage factor at device value, and click Calculate Earth Fault Current to calculate the Earth Loop Impedance and Earth Fault Current values.

    Calculate Cable Size

  10. To calculate the cable size, click the Size Cable button.

  11. If the core size is not found for the specified installation configuration, a message will be displayed to inform the user of this. Adjust the cable details and try again.

  12. Otherwise, the Sizing Result tab is then displayed:

  13. The Running Condition, Starting Condition, and Fault Protection fields are completed automatically when the Size Cable button is pressed.

  14. Clicking on the up arrow button on the Sizing Result tab (see below) will select a higher cable size from the cable catalogue. The application will then re-calculate the core size, current, voltage drop, and short circuit and earth fault calculations.

    Specify De-Rating Factor

  15. After the Size Cable button is clicked, the De-rating Factor section on the Cable Sizing tab displays calculated de-rating factor values, based on the cable installation configuration.

    The user can select a de-rating factor which will be used instead of the calculated value.

  16. To select a de-rating factor, click the De-rating Factors button. The Derating Factors window is then displayed:

  17. Select the required factor from the list. The list includes the de-rating factors that are part of the standard, and user-defined project specific de-rating factors set up in AVEVA Engineering.

    If a value is set at 1 then the rating will have no effect on the calculation.

  18. Click Save. The selected factor is then displayed in the Chosen De-rating Factor field.

  19. The Chosen De-rating Factor field value can only be set by the user to be equal to or less than the Calculated De-rating Factor field value.

  20. The User Changed checkbox indicates whether or not a factor has been changed by the user.

  21. If this field is blank when the Size Cable button is clicked, it will be automatically populated with the calculated value.

    Complete Sizing Fields

  22. Finally, click the Update button on the Sizing Result tab.

  23. If no suitable cable is found in the cable catalogue (see the table below), a message is displayed to inform the user of this. Either revise the cable details or add a suitable cable specification to the catalogue.

  24. If a suitable cable is found in the catalogue, the following Project Cable Data fields are then completed: Cable Number (an automatically generated number), Cable Type and Core Size.

    Note:
    In order for cable data to be selected from the cable catalogue, the following values in the window must match those of a cable or cables in the catalogue:

    Field name in Cable Sizing window

    Cable Catalogue field name

    Core Grouping

    CoreGrouping

    Single / Multi

    SingleOrMulti

    Material

    Material

    Insulation Type

    InsulationType

    Core Size

    CoreSize

    Units displayed next to Core Size field

    CoreSizeUnits

    Screened

    Screened

    Armoured

    Armoured

    Earth Core

    EarthCore

    Rated Voltage *

    VoltageDesc *

    * If the Rated Voltage / VoltageDesc field has a value then it is used to find a valid value in the Cable Catalogue grid. If the field has no value then does not search for a valid value in the Cable Catalogue grid.

  25. Click Save to save these details and exit the window.

    Note:
    For details of the cable sizing calculations, refer to the Common Functionality User Guide.

    Note:
    The maximum number of cables that may be connected to an equipment item may (optionally) be specified on the More Information window accessed from the Equipment Layout window. If the sizing procedure attempts to connect a cable to an equipment item when the maximum number of cables has already been connected to that item, a message is displayed to inform the user of this.

    Note:
    In the case of parent cables (i.e. cables with child cables), when a cable sizing update will result in the number of child cables changing, the Child Cable Numbering Options window is displayed when the cable is saved:



    Refer to Create a New Project Cable and Edit Project Cable Data for further information.

TitleResults for “How to create a CRG?”Also Available in